Figures
1-5
Introduction
Radiographic
testing of concrete slab floors in multistory buildings can provide
valuable information for building renovation and engineering evaluation
projects. A typical renovation project will require holes cored through
abovegrade floors for connections to utility services, duct work, communication
lines and anchor bolts. In an engineering evaluation, concrete reinforcement
size and placement information may be required to establish floor load
carrying capacity. Radiographic testing can reveal the internal features
of abovegrade floor slabs in order to avoid severing post tension cable
and electrical conduits in core cutting operations. These items may
be critical to current building tenants and require expensive repairs
if damaged. Repairs for post tension cable can cost tens of thousands
of dollars. Electrical service interruptions could be costly in terms
of lost work time due to downed computers or office lighting. Post tension
cable may, when cut, pop out of floors
and cause injuries. Coring personnel have been shocked when live wires
in electrical conduits were cut through. Radiographic testing is applicable
in preempting costly litigations that could arise from such accidents.
In keeping with the standardization trend of the NDT industry, the development
of defensible techniques for radiographic testing of abovegrade concrete
floors is indicated. Independent NDT labs offering this service should
consider treating this subject as seriously as any code radiography
æ in other words, with the highest degree of integrity. It is hoped
that the information presented here will advance this highly visible
application of radiographic testing.
Radiographic
testing of concrete slab floors can provide invaluable information
in building renovation.
Safety Considerations
No discussion of radiographic testing, especially when it is to
be performed in public areas, should begin without a thorough treatment
of safety considerations. Radiographic testing operations must, by law,
adhere to the radiation licensee's operating and emergency procedures
deriving from the agreement state agency or the Nuclear Regulatory Commission
rules. It may be advisable to include a section in these procedures
dealing expressly with concrete radiography due to the potential proximity
of the public. The safety goal is the limitation of the radiation dose
to levels as low as reasonably achievable. Radiographic testing crews
must be especially vigilant in their safe operating practices in public
environments. Radiographic testing to be performed in specific locations
may require special security measures. Examples of such locations are
hotel lobbies, schools, hospitals and airports. Some sites will require
additional personnel beyond the mandatory two person radiographic testing
crew posted to guard the entrances of restricted areas.
Faced with a job at a highly vulnerable
site, a useful strategy is to call the Nuclear Regulatory Commission
or the agreement state agency having jurisdiction over the operation
and request a site audit. Agency audits can benefit radiographers by
documenting their adherence to regulations. These agencies gain valuable
experience when responding to such radiographic testing licensee requests.
The firsthand information gained by the agency may avert a public relations
disaster or lawsuit and cooperation between regulatory agencies and
their licensees boosts the credibility of the radiographic testing community.
In planning radiographic testing operations, the public must always
be considered first. Proper protocol demands routing notifications of
scheduled radiographic testing operations to all interested parties
through building management. Tenants of spaces to be entered for source
or film placement or radiation surveys need to be informed well in advance
of the work. After hours security and cleaning workers must also be
informed of the radiographic testing schedule. Besides these notifications,
agency approved barricades should be placed as necessary and guards
stationed at strategic entry points to prevent unauthorized persons
from entering restricted radiation areas. Mistakenly assuming that everyone
has been informed and will cooperate can lead to extremely compromising
situations.
Members of the public must be guaranteed
unrestricted areas, where dosage levels do not exceed regulatory limits.
It is prudent to assume that minors may be in the population when considering
these dosage limits. If a space near a radiographic testing operation
is not surveyed, the radiographer is thereby assuming that the radiation
levels will be below regulatory limits. Of course, the agencies require
that the radiographers perform physical radiation surveys of restricted
area boundaries. Radiation levels in office buildings can be especially
unpredictable compared to more familiar industrial sites. Authorized
security personnel should be enlisted to ensure that relevant areas
are truly unoccupied. Assuming that any space is vacant without personal
verification by the radiographer in charge can become a regrettable
error. Only authorized radiographic testing personnel should have access
to radiation areas. Under normal circumstances, everyone should get
permission from the designated radiographer in charge before entering
posted radiation areas. Radiographic testing personnel, besides their
usual array of dosimetry and survey meters, should ideally be equipped
with twoway radios. Instantaneous communication is essential to safe
radiographic testing operations where personnel are typically out of
each other's sight. The cost of the radios will be negligible compared
to the enhanced safety and security they afford. Placement of radiographic
testing personnel and control of the public aside, proper source exposure
techniques can limit the radiation field to a great degree. Agency regulations
specify that a collimator be used. To further attenuate extraneous radiation,
lead shotbags may be packed around a collimator placed on a suitably
stout stand. This extra shielding isn't always necessary but can be
very useful when needed. The majority of the techniques presented here
assume placing the source above and the film below the floor under investigation.
The utility of this arrangement will become apparent later as the need
for surface markers is developed. Film above/source below techniques
are quite possible, though perhaps more cumbersome.
Radiation Source Selection
The radiation source used for a particular job should ideally be selected
on the basis of the ability to complete a properly set up exposure as
quickly as possible. Safety, concrete thickness, size of cores, number
of planned exposures, site access and overall costs are also factors
involved in radiation source selection. Two isotope radiation sources
are used for the bulk of commercial radiographic testing, Ir-192 and
Co-60. Ir-192 can handle up to 203 mm (8 in.) thickness, while Co-60
can handle up to 406 mm (16 in.). Co-60 may, of course, be used on thinner
floors, especially where there are many exposures to be made. Site access
may limit a radiographer's isotope choices. An Ir-192 exposure device
weighing less than 22 kg (50 lb) may be hand carried, while a Co-60
device may weigh 222 kg (500 lb). Co-60 costs are higher than those
for Ir-192. However, the greater energy and radiation output of Co-60
over Ir-192 may reduce costs in cases where many exposures are planned
or the concrete thickness makes Ir-192 exposures excessively long. Co-60
can typically be setup at much greater source to film distances than
Ir-192, which can reduce image distortion.
Distortion in Concrete Coring
Two factors creating undesirable distortion in concrete coring radiography
are image enlargement and shift. A reinforcing bar close to the sourceside
of a floor will appear enlarged relative to one closer to the filmside.
Objects farther from the center of the exposure will appear shifted
from their true locations. These effects trouble many radiographers
because of the unfamiliarly thick sections encountered in concrete structures.
However, confidence may be gained through the use of readily understandable
geometry and consistent practice in proper techniques. The geometry
of distortion demands that a larger diameter core or thicker concrete
require a greater source to film distance. In some instances, a larger
film area, supplied by multiple cassettes, can substitute for source
to film distances. A greater source to film distance will always minimize
distortion. Thinner concrete will produce a less distorted image for
a given exposure setup. When planning exposures, there are certain factors
and issues to be kept in mind. Typical exposure geometry is illustrated
in Figure 1.
Calculating Core Diameter
Radiation proceeds through the floor in a cone shaped pattern as indicated
in Figure 1. The central ray is
perpendicular to the floor and the film plane. An area of the floor
surface is thus enlarged onto the film below. Note that the size of
the radiograph does not directly indicate the area of the floor surface
imaged. This discrepancy must be dealt with or assumptions will be made
about the contents (or lack thereof) in areas not imaged by the radiograph.
Concrete thickness, source to object
distance and total source to film distance must be factored into a calculation
that will predict the maximum core diameter imaged by a given film size.
This sourceside surface area may be termed the actual film size. An
equation is used to find the actual film size that a given technique
will yield. A correction factor, which can be used to calculate the
dimensions of floor surface area imaged, is found as follows: source
to object distance divided by the total source to film distance equals
the correction factor. The correction factor multiplied times a film
dimension, length or width, yields the actual floor surface imaged in
that direction. Hence, if one multiplies the film length by the correction
factor, then multiplies the film width by the correction factor, then
takes the products of both equations and multiplies them, one can determine
the actual film size. Correcting to the actual film size yields the
length and width of sourceside floor surface imaged. The proper source
to film distance will produce an image comfortably containing an anticipated
core diameter and allow for minor film misalignment in a reasonably
short exposure time. This area will always be smaller than the dimensions
of the film in the cassette. This process is illustrated in
Figure 2.
Here, the resulting actual film size
equals approximately 295 by 359 mm (11.6 by 14.1 in.). With the technique
illustrated above, a 203 mm (8 in.) diameter core could be imaged with
room to spare on a properly centered film. As to physically centering
a film for exposure, only the perpendicular central ray of a radiation
source goes straight through a floor. Lacking a nearby penetration in
the floor from which to measure, lining up a cassette within an inch
or so of the core's center can be a real challenge. Plumb bobs, long
tapes, careful measurements and maps are useful tools in this vital
step. Some radiographers have reported the use of magnets and compasses.
Tapping with a hammer and listening may get you close. Convenient pilot
holes, made with hammer drills and small diameter bits, have been known
to cut through the very items the radiographic testing was intended
to protect. Anyone who has looked at a misaligned radiograph will agree
that however it is accomplished, accurate alignment is absolutely essential
to the process.
Multiple, overlapped films may be
placed to increase actual film size when using a short source to film
distance, imaging a large diameter core or attempting to compensate
for questionable film alignment. Increased distortion in both image
enlargement and shift will result from a shorter source to film distance.
This condition may be acceptable, especially where thinner floors or
smaller holes make distortion less of an issue. Thus, the source to
film distance can be maximized to increase actual film size or minimized
to shorten the exposure time. In any case, image enlargement is the
main concern here. One must ensure that the source to film distance
selected, having taken into account floor thickness and core diameter,
will produce an actual film size large enough to contain the entire
core volume.
Tricks of the Trade
Besides minimizing distortion, the use of sourceside markers ensures
that holes may be marked for coring with a reasonable safety margin.
To prove that a technique is providing adequate radiographic data to
core safely is of paramount importance. The potential for liability
demands doing the math beforehand. Calculations aside, the efficacy
of any setup may be proven empirically by using sourceside markers.
Therefore, on the source side of the floor the outline of the core should
be marked with a lead ring. This ring can be formed from a strip cut
from readily available 3 mm (0.1 in.) lead sheet. This ring, the most
enlarged object in the radiograph, defines the conical volume of the
core. Any contents revealed within the image of the ring lie either
in the path of the core bit or very close. The ring and any other markers
used should be indexed to the floor quite carefully. Lead letters (include
some that cannot be read reversed in the image, such as the letter R),
should be used to identify the film. For the best future reference,
the whole surface marker arrangement may be preserved with spray paint.
These tricks of the trade can be readily appreciated and understood
by all involved in the coring operation, once they view the finished
radiograph, even if the preexposure math escapes them.
Image Shift
Image shift is another concern altogether, but no less important. Ideally,
the lead ring should be centered up below the source on the floor. This
will center the ring's image on a properly placed film. A plumb bob
may be used to align the center of the lead ring with the central ray
of the radiation source. A suitable lead marker, such as a fishing sinker,
should be placed on this center. This marker can also indicate a compass
direction on the film for orientation purposes when interpreting the
results. The lead ring and center marker on the floor surface will be
the objects whose images are the most enlarged (both) and/or shifted
(the ring). The central ray images the only nonshifted point on the
radiograph. The degree of shift of a feature is dependent upon height
in the floor and the distance of the feature from the central ray. These
relationships are illustrated in Figure
3. The farther an item is from the film plane or from the central
ray, the more the image of that feature will be shifted in the radiograph.
Once again, the parameter most readily under the radiographer's control
is source to film distance. The greater the source to film distance,
the less the radiographic image will be shifted and enlarged. This principle
is illustrated in Figure 4.
Keeping these geometrical facts in
mind simplifies the interpretation of the radiograph. As previously
mentioned, using the surface markers takes the worry out of the process.
If no item (conduit, cable, rebar) is revealed within the circumference
of the image of the lead ring, the floor may be cored with relative
impunity. If items are present in the circumference of the lead ring,
the proposed hole can be relocated and subsequent exposures may reveal
a clear area. The image shift mechanism is predictable and quantifiable
with geometric calculations if enough of the variables involved are
known. An application of this principle is the determination of depth
of discontinuities in a thick section. This procedure is described in
the Nondestructive Testing Handbook, second edition: Volume
9, Special Nondestructive Testing Methods.
Rebar Depth Determination
A floor's load carrying capacity can be determined by depth and
size of rebar. Building occupancy permits typically hinge on a professional
engineer's certification of the floor load carrying capacity. If archival
blueprints cannot be produced, radiographic testing may be used to image
the structural concrete reinforcements. Using the aforementioned techniques
and careful workmanship, reinforcement bar in abovegrade slabs can be
located, sized and its depth in the floor determined. To begin the radiographic
testing data gathering, it is a good idea to start with one conventional
exposure through the floor. This will verify exposure time and orientation
of rebar to be studied. The bars must be running perpendicular to the
direction the source will be moving and also perpendicular to a line
drawn between the surface markers. Using the technique described in
the Nondestructive Testing Handbook, a double exposure or parallax
radiograph is produced. Source side markers are placed so that during
the first half of the exposure, one will be imaged through the floor
locating the source's central ray and the other marker will be shifted.
On the second half of the exposure, after moving the source, the central
ray will image the previously shifted marker and the original central
ray marker will be shifted. Comparison of the shifts and careful measurements
taken from the setup can yield depth location of features. Once the
rebar depth is known, divide the source to rebar distance by the total
source to film distance. This yields a correction factor, which, when
multiplied times the measured rebar image, yields the actual rebar size.
In this technique, the floor thickness must be known. In the alternate
technique illustrated in Figure 5,
the floor thickness need not be known initially. One radiograph is produced
to establish an exposure time, film alignment and subject rebar orientation.
The second exposure (on a fresh film) is set up according to
Figure 5. Accurate measurements and data records are necessary for
successful calculations.
For
Figure 5, assume that M and L/3 are known and
T is unknown. Using the rule of triangles,
| (1) |
 |
we can determine that
| (2) |
 |
| (3) |
 |
| (4) |
 |
| (5) |
 |
Tan q,
Dc and M are known; thus T can
be calculated using the equation
| (6) |
 |
or
| (7) |
 |
While depth determinations are fairly
rigorous, interpreting radiographs for safe core cutting locations involves
little more than identifying surface markers and images of internal
items in the floor. Post tension cable resembles roughly stranded rope:
a distinctly nonhomogenous, striated density with no terminations. Rebar
may show upsets (bumps) in profile, tie wire, terminations and a homogenous
density throughout. Plastic conduits will evidence an increase in film
density due to the void, with lighter copper conductor wire visible
inside. A film density of 1.8, measured through the concrete alone,
is usually sufficient for interpretation. Clients will also be able
to view lower density film using commonly available lighting. Some clients
prefer to read films themselves, although most will leave the interpretation
to the radiographers. A white china marker is useful to indicate shot
numbers, floor numbers, center markers and core outlines. Critical items
such as post tension cable and conduits should not be marked so closely
as to obscure their outlines. Due to the possibility for onerous and
avoidable communication mistakes, the radiographer in charge should
always make sure that clients have all of the information they need
to core with confidence. It must be emphasized that once the indexing
marks on the floor are gone, the radiographic testing data may be useless.
Conclusion
One last word is appropriate to those unfamiliar with concrete radiographic
testing. Concrete is a variable radiation absorber compared to a fairly
predictable one such as steel. To establish and maintain proper exposure
times with the chosen radiation source, especially where exact floor
thickness is unknown or variable, a direct reading pocket dosimeter
may be placed behind the film to record a relative dose. The dosimeter
reading necessary to achieve a proper film density will have to be determined
experimentally. Generally, the fastest lead screen industrial radiography
films available are ideal for concrete radiographic testing. The lead
screens themselves do not have to be code quality and a 0.3 mm (0.01
in.) thickness front and back will suffice. If the exposure geometry
is correct as outlined above, the radiographic sensitivity using fast
film with lead screens will be adequate for interpretation. Successful
fluorescent screen techniques have been reported. However, due to the
cost of the screens themselves and their usually required hard cassettes,
the savings in exposure times may not save money overall. Handling of
these heavy cassettes may well be a formidable challenge to the radiographer
hauling armloads of them up flights of stairs.
Acknowledgments
Many of the techniques described here evolved over more than a decade
of practical radiographic testing experience. The author extends recognition
to the management, technicians and engineers at Reinhart and Associates,
Inc., in Austin, Texas.