Figures 1-4
Figures 5-7
Figures 8-10
INTRODUCTION
This paper provides a description of the ultrasonic
nondestructive tests that were performed on a high level radioactive waste
storage tank which has been in service for 46 years at the Department of
Energy's Savannah River site, near Aiken, South Carolina. These tests were
performed in accordance with WSRC-TR-2002-00061 (Wiersma et al., 2002). The in
service testing program for high level waste tanks was developed using
BNL-52527 (Bandyopadhyay et al., 1997) for waste tank in service testing
programs as a guide.
The tests were performed from the contaminated, 762 mm
(30 in.) wide annular space of the inactive, 3.9 ML (1.03 x 106 gal),
underground waste storage tank. A steerable, magnetic wheel wall crawler was
used to simultaneously collect data with up to four ultrasonic transducers and
two cameras.
NDT
of the tank included remote automated ultrasonic testing supplemented by remote
visual testing.
The purpose of this test was to verify known corrosion
models and to investigate the possibility of previously unidentified corrosion
mechanisms. The tests included the testing of previously identified leak sites
as well as thickness mapping and crack detection scans on specified areas of
the tank covering welds and all past and present interface levels.
Tank Design
Figure 1 shows a schematic of the type of waste tank
that was tested. The following is a summary of the tank features:
- construction - 1955 through 1956; entered high level
waste storage service in 1960
- capacity - 3.9 ML (1.03 x 106 gal)
- material - ASTM A285, grade B carbon steel (not
stress relieved)
- construction code - ASME-52
- 1.5 m (5 ft) steel secondary containment pan -
material is A285; grade B carbon steel
- annulus ventilation - normally positive pressure
(changed to negative during testing)
- annulus access - constructed with 127 mm (5 in.)
carbon steel risers at the south, west, north and east annulus risers.
Additional access provided through 152 mm (6 in.) diameter drilled testing
ports. There are 12 testing ports plus the four 127 mm (5 in.) risers spaced
around the 81.4 m (267 ft) circumference of the tank. The testing ports are
identified by the distance in feet from the south riser (Figure
2).
NDT REQUIREMENTS
The in service testing program for high level waste
tanks dictates the frequency and extent of the areas to be tested, as well as
the damage mechanisms to be detected. The program states that the specific
tank "shall be inspected two times within a five-year time span to validate
current degradation models. Known leak sites will be characterized in addition
to the normal extent of examination. If leakage occurs in unexpected regions
and unknown degradation mechanisms are suspected, additional inspections will
be performed" (Wiersma et al., 2002).
The in service testing program for high level waste
tanks calls for the following regions of a high level waste tank to be tested:
- liquid vapor interface
- liquid sludge interface
- upper weld of lower knuckle of primary tank (5% of
accessible circumference)
- lower knuckle base material
- external surface of primary tank (includes vapor
space)
- vertical and horizontal welds other than the lower
knuckle weld (one vertical course section and 5% of middle horizontal weld).
These general requirements are further delineated in a
tank specific test plan. The tank specific plan stipulated the following tests
specific to the primary wall:
- four vertical strips for the entire accessible height
of the tank, one each under risers IP55, IP107 and IP182 as well as the east
riser (Figure 2)
- 9.1 m (30 ft) of middle horizontal weld between riser
IP171 and IP207 (10% of circumference - additional 5% in lieu of 5% of upper
weld of lower knuckle which was inaccessible due to tank geometry)
- lower primary shell plate vertical weld below riser
IP182
- five previously identified leak sites.
Figure 2 illustrates the approximate radial location of
annulus access risers. Locations are in feet from the south riser. The north,
south, east and west risers are 127 mm (5 in.) carbon steel pipe. The other
testing ports were added using a 152 mm (6 in.) diameter core drill.
NDT TECHNIQUES
NDT of the tank included remote automated ultrasonic
testing supplemented by remote visual testing. The following techniques were
used to test the tank:
- thickness mapping
- weld testing/crack detection
- ultrasonic discontinuity sizing
- through wall bleed out.
Testing Equipment
All ultrasonic tests were performed using an automated
ultrasonic system and a remotely operated magnetic wheel scanner. The
prescribed regions were tested utilizing two basic data collection techniques:
- vertical strips - base material thickness mapping and
crack detection scans
- weld testing - scans of weld and heat affected zones
to detect and characterize cracking oriented parallel or perpendicular to the
weld seam.
Ultrasonic System
The ultrasonic system used for these tests is capable of
performing tests with multiple transducers and techniques simultaneously. It
is also capable of performing thickness mapping, weld testing and A-scan
recording all at the same time. During tank tests, it was used to operate two
angle beam and one thickness mapping transducer or four angle beam probes
simultaneously. It is operated through a laptop computer as the user
interface. The system also controls the wall crawler.
Wall Crawler
The wall crawler (Figure 3) is a commercially available
crawler, which attaches to the steel tank wall through strong, permanent
magnetic wheels. It is capable of being installed through a 127 mm (5 in.)
carbon steel riser. It can scan with up to four transducers. The wall crawler
is typically outfitted with a remote control pan and tilt camera system with
auxiliary lighting.
The wall crawler included a pneumatically activated
camera boom arm to lift the pan and tilt camera about 254 mm (10 in.) off the
surface. It also has pneumatic lifting feet to decouple it from the tank wall
to allow removal from the annulus.
Procedure and Equipment Qualification
The in service testing program for high level waste
tanks states that the ultrasonic system (instrument, transducer, scanning
device and cables) shall have the following detection capabilities (tested at
12.7 mm [0.5 in.] nominal thickness of the tank sidewall plate):
- general corrosion/thinning detection greater than 0.5
mm (0.02 in)
- pitting detection (elliptical or hemispherical)
greater than 1.3 mm (0.05 in.) depth
- crack detection greater than 2.5 mm (0.1 in.) deep and
greater than or equal to 12.7 mm (0.5 in.) long. In the absence of an
acceptable cracked sample, a machined notch 1.3 mm (0.05 in.) deep by 25.4 mm
(1 in.) long can be used instead of a crack for qualification.
The procedures and equipment easily met the above
requirements (Elder, 2002).
Thickness Mapping
Thickness mapping includes wall thickness measurement as
well as the detection and sizing of corrosion, pitting and liquid/air
interface attacks. Thickness mapping was performed in four vertical strips.
Individual vertical strips were 216 mm (8.5 in.) wide so the combined width of
all four strips provided coverage of 1% of the circumference of the tank.
Thickness mapping data were collected over the entire accessible height of the
tank to ensure coverage of all areas and environments in the tank. By
collecting data in a continuous strip from top to bottom, all present and
historic interface levels are examined as well as the vapor space of the tank.
Thickness mapping data were collected using the
automated ultrasonic system. A thickness mapping program was utilized to
provide color coded thickness plots from the top, side and end views. These
data were collected using a dual element, 0 degree, longitudinal wave
transducer operating at 5 MHz.
Weld Testing and Crack Detection
Weld testing and crack detection were performed with the
same ultrasonic system using amplitude based weld testing software. Crack
detection was performed using single element, 45 degree shear wave transducers
operating at 4 MHz. This technique was incorporated into the thickness mapping
vertical strips and was used to examine welds for cracking oriented parallel
and perpendicular to the weld seam.
Ultrasonic Discontinuity Sizing
When indications were detected with ultrasonic
techniques, the extent of the indications were measured. The location and
length/width in the X and Y directions were determined based on where the
indication was discernable from the background noise or thickness.
Pitting indications were reported based on the remaining
sound metal (ligament) above the pit. The depth of any pit indications was
determined by subtracting the minimum thickness reading obtained from the pit
from the thickness of the area adjacent to the pit.
Cracking lengths were reported to the points where the
indication was no longer discernable from the noise. Crack depths were
determined utilizing planar discontinuity sizing techniques. Using the same
transducers that were used for detection, the amplitude was adjusted to locate
the deepest point on the crack. When indications were less than 100% through
wall, a measurement of the remaining metal (ligament) was made using the
absolute arrival time technique. The absolute arrival time technique is a
planar discontinuity sizing technique used throughout industry that provides a
direct reading of depth to the crack tip.
Through Wall Bleed Out
Through wall bleed out is the term being used to
describe the field implemented variation of a liquid penetrant surface test
technique. It was noted that the water being used for an ultrasonic couplant
would penetrate (through capillary action) surface cracks. Due to the elevated
temperature of the tank wall (around 322 K [120 °F]), the wetted surface
would dry after a few minutes. Where there was a crack open to the exterior
surface, the water drawn into the crack would then bleed out, providing a high
contrast image of the open crack. Video cameras were used to view these
indications and make crude measurements of length as the crawler was driven
along the indications. Figure 4 shows an example of the video image of the
bleed out region.
NDT DATA COLLECTION
Field Conditions
Tests were performed from the annular space of the high
level waste tank. The wall crawler and cameras were installed in the annulus
and operated from the NDT control trailer which was up to 61 m (200 ft) from
the riser. Access to the annulus was through testing ports or risers inside
contamination control huts. These risers are approximately 1.2 m (4 ft) long
and are either 127 mm (5 in.) carbon steel pipe or 152 mm (6 in.) diameter
concrete holes. All ultrasonic tests were performed by inserting the wall
crawler through the 152 mm (6 in.) concrete risers. Remote pan and tilt
cameras were also inserted into the annulus to monitor crawler movement. The
tank has a history of through wall leaks, therefore the annulus is
contaminated. The tank ventilation was shut down and auxiliary ventilation was
installed to provide negative pressure ventilation during the tests. Huts were
set up around each riser that was used for crawler access to provide
contamination control. In addition to the huts and ventilation, respiratory
protection was typically required during crawler installation, removal and
maintenance activities.
Test Areas
All of the required tests were performed by deploying
the crawler through three risers. Ultrasonic tests were performed with the
wall crawler in risers IP55, IP107 and IP182.
NDT RESULTS
All test data were analyzed by certified Level III
personnel.
Summary of Test Results
The tested tank was not stress relieved and had a
history of stress corrosion cracking with 18 previously identified leak sites
(Waltz and West, 2001). The tank is presently an inactive tank.
Several leak sites were selected to be ultrasonically
tested to determine the length, depth and contributing factors (for example,
weld attachments, weld beads and so on) of cracks. These indications are
scheduled for retesting in five years to look for any changes and to test
crack growth. Maximum crack lengths were determined to be longer than
previously expected but still well within the established critical crack
lengths at the crack locations (Wiersma and Elder, 2003).
Thickness mapping was performed on 1% of the tank
circumference for the entire accessible height of the tank (Figure
5). This
thickness mapping was performed to detect and measure any general wall loss,
pitting or interface attack in all regions of the tank including the vapor
space. No reportable wall loss or pitting was detected.
Vertical Strip Results
Tests of the tank through riser IP55 included one
vertical strip for the entire accessible height of the tank. No reportable
areas were detected in the vertical strip. The minimum thicknesses detected in
the upper and lower plates are above nominal thickness. The minimum thickness
detected in the upper plate was 16.2 mm (0.639 in.) and is near the edge of
the plate toward the middle weld. The minimum thickness detected in the lower
plate was 16.05 mm (0.632 in.). This minimum thickness area is a 6.4 by 10.2
by 0.8 mm (0.25 by 0.4 by 0.03 in.) deep indication approximately 63.5 mm (2.5
in.) from the middle weld. The minimum thickness at the bottom of the same
plate is 16.1 mm (0.634 in.). The indication inside the black circles on
Figure 6 was approximately 0.8 mm (0.03 in.) deep. The results also show the
plates to be thinner at the edges. There are several noise spikes shown in the
side and end views. These noise indications were tested and determined to not
be relevant. No cracklike indications were detected in this strip.
Previous Indication Investigation
One previously identified indication in the upper plate
vertical weld at approximately 16.2 m (53 ft) was also examined under riser
IP55. The indication was observed at 5.1 m (200 in.) above the tank bottom.
Due to the high weld profile and limited time and the fact that the
examination of this leak site was not a requirement of the test scope, the
indication was only tested from one side of the vertical weld. The tests were
performed on the side of the weld opposite the riser. The crack was confirmed
to be through wall, but also had a partial through wall segment. Measuring the
indication on the right side only, the through wall portion was 35.6 mm (1.4
in.). The total length was 94 mm (3.7 in.) on that side of the weld.
Figure 7 shows some of the ultrasonic data from this
indication. The through wall portion of the crack is represented by the blue
portion of the ultrasonic data in Figure 7. The yellow and green portions of
the ultrasonic image indicate the part of the crack that is only partially
through wall.
Weld Testing Results
The following is a summary of the indications detected
in the lower plate vertical weld. The through wall indication (Figure
8)
measured 114 mm (4.5 in.) total length. The photographic overlay is from a
liquid penetrant test performed on a similar tank in 1962. The recently
detected crack is nearly identical to the crack from 1962.
Approximately 10.1 m (33 ft) of the middle horizontal
weld was tested for horizontal and vertical cracking. The middle horizontal
weld was examined in three sections, as noted:
- from 52.1 to 54.9 m (171 to 180 ft)
- from 55.8 to 59.4 m (183 to 195 ft)
- from 59.7 to 63.4 m (196 to 208 ft).
Previously identified leak sites on the middle weld were
also tested.
Leak Site
The leak site at 58.5 m (192 ft) is a horizontal/arched
crack in a lower plate at a weld repair location (Figure
9). The through wall
portion (verified visually with the bleed out technique) of this crack was
measured ultrasonically to be 259 mm (10.2 in.). The indication is arch shaped
around a weld repair region in the horizontal weld. The weld repair area
appears to be approximately 203 mm (8 in.) long and centered on the through
wall portion of the crack. The total length of the indication was measured at
460 mm (18.1 in.). As shown in Figure 10, this indication is longer at the
inside surface than on the outside.
CONCLUSION
A new ultrasonic in service test program for high level
waste tanks at the Savannah River site has been implemented. The test details
and results from the testing of a specific tank that has been in service for
over 40 years have been summarized.
No indications of reportable wall loss or pitting were
detected. All thickness readings were above minimum design thickness. Several
small indications of thinning were detected. The crack detection and sizing
tests detected five previously undetected indications, four of which were only
partially through wall. The lengths of cracks that were examined were slightly
longer than expected, but well below instability lengths.
ACKNOWLEDGMENTS
The authors gratefully acknowledge the outstanding work
of the Savannah River site waste tank ultrasonic testing team of E.R. Holland
and R.W. VandeKamp. The work was supported by the United States Department of
Energy under contract number DE-AC09-96SR18500.
REFERENCES
Bandyopadhyay, K., S. Bush, M. Kassir, B. Mather, P.
Shewmon, M. Streicher, B. Thompson, D. van Rooyen and J. Weeks, BNL-52527,
Guidelines for Development of Structural Integrity Programs for DOE High Level
Waste Storage Tanks, Engineering Research and Applications Division, Upton,
New York, Brookhaven National Laboratory, January 1997.
Elder, J.B., "Procedure and Equipment Qualification,"
TSD-NDE-20020726, Aiken, South Carolina, Savannah River National Laboratory,
December 2002.
Waltz, R.S. and W.R. West, "Annual Radioactive Waste
Tank Inspection Program - 2000," WSRC-TR-2001-00149, Oak Ridge, Tennessee,
US Department of Energy, Office of Scientific and Technical Information, May
2001.
Wiersma, B.J. and J.B. Elder, "Structural Evaluation of
Flaws Detected during Ultrasonic Examination of a High Level Radioactive Waste
Tank," Proceedings of the ASME Pressure Vessels and Piping Conference, New
York, ASME International, July 2003.
Wiersma, B.J., K.H. Subramanian, R.L. Sindelar, M.E.
Dupont, J.B. Elder, W.R. West, R.S. Waltz and V. Cech, WSRC-TR-2002-00061,
In-service Inspection Program for High Level Waste Tanks, US Department of
Energy, Office of Scientific and Technical Information, February 2002.
* Savannah River National
Laboratory, Materials Technology Section, Aiken, SC 29808; (803) 725-9844; fax
(803) 725-1744; e-mail <james.elder@srs.gov>.
Copyright © 2004 by
the American Society for Nondestructive Testing, Inc. All rights reserved.
Copyright © 2008 by the American Society for Nondestructive Testing, Inc. ASNT is not responsible for the authenticity or accuracy of information herein. Published opinions and statements do not necessarily reflect the opinion of ASNT. Products or services that are advertised or mentioned do not carry the endorsement or recommendation of ASNT.
IRRSP, NDT Handbook, The NDT Technician and www.asnt.org are trademarks of the American Society for Nondestructive Testing, Inc. ACCP, ASNT, Level III Study Guide, Materials Evaluation, Nondestructive Testing Handbook, Research in Nondestructive Evaluation and RNDE are registered trademarks of the American Society for Nondestructive Testing, Inc.
ASNT exists to create a safer world by promoting the profession and technologies
of nondestructive testing.